Domestic Control Valves

RAVK



RAVK

RAVK

Technical data



Code number 013U8063 
PN 16  bar
Min. setting temp. 25  °C
Max. setting temp. 65  °C
Capillary length 2  m
Gain Ks 0.35  mm/°C
Max. sensor temp. 120  ° C
Max. ambient temp. at sensor 120  ° C
Sensor connection R 1/2 
Remarks RAVK can be combined with RAV-/8, VMT-/8, VMA and KOVM valves. RAVK max. temperature 120°C.  

Accessories



017-4369 Sensor pockets
017-4370 Sensor pockets